AX-DUCT SERIES
The Axiom Thermal AX-DUCT series is an insert-type duct temperature sensor: a passive resistive sensor designed for HVAC, building automation and industrial duct temperature monitoring. The NTC thermistor converts temperature changes into precise resistance variations for continuous measurement and feedback control of air temperature in ducts. High-protection plastic housing and stainless-steel probe rod for long-term stability.
Air-handling units, supply and return air ducts, ventilation and heat recovery, building automation (BMS), industrial duct temperature monitoring.
| Sensor chip | NTC thermistor, 10K / 20K (others on request) |
| B value | 3950 K (customisable) |
| Measuring range | −40 … +125 °C (customisable) |
| Accuracy class | ±1% at 25 °C (±0.3 °C) |
| Operating voltage | Passive (no external power; resistance read by the controller) |
| Output signal | Resistance, negative exponential dependence on temperature |
| Probe length | 150 / 200 / 300 mm (custom lengths) |
| Probe material | Stainless steel |
| Wiring | 2-wire, no polarity |
| Operating ambient temp. | −20 … +70 °C (housing) |
| Operating humidity | 0 … 96% RH (non-condensing) |
| Storage | −20 … +70 °C; 20 … 60% RH |
| Protection rating | IP65 |
| Code | Description |
|---|---|
| AX-DUCT-N10K-150 | NTC 10K B3950, probe 150 mm, IP65 |
| AX-DUCT-N10K-200 | NTC 10K B3950, probe 200 mm, IP65 |
| AX-DUCT-N10K-300 | NTC 10K B3950, probe 300 mm, IP65 |
| AX-DUCT-N20K-200 | NTC 20K B3950, probe 200 mm, IP65 |
| Element / B value | Other NTC values and B values on request |
| Range | Custom measuring range |
| Probe | Custom length; optional matching mounting tube |
| Warranty | 12 months from date of shipment (repair or replacement) |
Installation: (1) drill a hole in the duct wall matching the probe diameter; (2) insert the probe so that it is fully in the airflow; (3) connect the wires to the marked terminals (NTC 2-wire, no polarity) and close the housing; (4) keep away from VFDs, motors and other high-power interference; (5) mount in a stable airflow zone, away from bends and air outlets; (6) the probe must not touch the duct wall; (7) route cables away from power lines, shielded cable recommended. Commissioning: check wiring for short or open circuits, read the resistance with the controller or a multimeter and compare with the R/T table; controller offset ±2 °C; run 30 minutes and check that the reading is stable. Never exceed the rated temperature or bend the probe.
Specifications subject to change without notice. Full resistance tables and dimensional drawings are included in the PDF datasheet.
Tell us the model, quantity and destination. We will get back to you as soon as possible.
Contact usWe use cookies to improve your experience on our site. By using our site, you consent to cookies.
Manage your cookie preferences below:
Essential cookies enable basic functions and are necessary for the proper function of the website.
You can find more information in our Cookie Policy and Privacy Policy.